Min Pre Alarm [418]
Min Pre Alarm Margin [4181]
With load type Basic, [415], used the Min Pre-Alarm
Margin sets the band under the Normal Load, [41B], menu
that does not generate a pre-alarm. With load type Load
Curve, [415], used the Min Pre-Alarm Margin sets the band
under the Load Curve, [41C], that does not generate a
pre-alarm. The Min Pre-Alarm Margin is a percentage of
nominal motor torque.
In case of Load Curve R, the margin is percentage of Load
curve torque at the actual speed.
Min Pre Alarm Response delay [4182]
When the load level without interruption is below the alarm
level longer than set “Min PreAlarm delay” time, a warning
is activated.
With load type Basic, [415], used the Min Alarm Margin
sets the band under the “Normal Load [41B]”, menu that
does not generate an alarm. With load type “Load Curve
[415]”, used the Min Alarm Margin sets the band under the
“Load Curve [41C]”, that does not generate an alarm. The
Max Alarm Margin is a percentage of nominal motor
torque.
In case of Load Curve R, the margin is percentage of Load
curve torque at the actual speed.
Min Alarm Response delay [4192]
When the load level without interruption is below the alarm
level longer than set “Min Alarm delay” time, an alarm is
activated.
The Autoset Alarm function can measure the nominal load
that is used as reference for the alarm levels. If the selected
“Load Type [415]” is Basic it copies the load the motor is
running with to the menu “Normal Load [41B]”. The
motor must run on the speed that generates the load that
needs to be recorded. If the selected “Load Type [415]” is
Load Curve it
performs a test-run and populates the “Load
Curve [41C]” with the found load values.
The default set levels for the (pre)alarms are:
These default set levels can be manually changed in menus
[416] to [419]. After execution the message “Autoset OK!” is
displayed for 1s and the selection reverts to “No”.
4181
MinPreAlMar
Default:
10%
Range:
0-400%
4182
MinPreAlDel
Default:
0.1 s
Range:
0-90 s
4191
MinAlarmMar
Default:
15%
Range:
0-400%
4192
MinAlarmDel
Default:
0.1 s
Range:
0-90 s
WARNING!
When autoset does a test run the motor
and application/machine will ramp up to
maximum speed.
NOTE: The motor must be running for the Autoset
Alarm function to succeed. A not running motor
generates a “Failed!” message.
41A
AutoSet Alrm
Default:
No
No
0
Yes
1
Overload
Max Alarm
menu [4161] + [41B]
Max Pre Alarm menu [4171] + [41B]
Underload
Min Pre Alarm menu [41B] - [4181]
Min Alarm
menu [41B] - [4191]
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......