CG Drives & Automation 01-7491-01r0
185
-100%AnOut1 has a negative 100% output value
65%AnOut2 has a 65% output value
The example in fig. 153 indicates that both the Analogue
outputs are active.
I/O board Status [728] - [72A]
Indicates the status for the additional I/O on option boards
1 (B1), 2 (B2) and 3 (B3).
These menus are not visible in the control panel display.
Only used in EmoSoftCom PC-tool (optional) and can be
read via fieldbus or serial communication.
Status bits 0 to 15.
See Chapter 10.2.1 page 85.
Status bits 16 and up.
See Chapter 10.2.1 page 85.
VIO Status [72C]
Shows the values of the 8 Virtual IO´s in menu[560].
11.7.3
Stored values [730]
The shown values are the actual values built up over time.
Values are stored at power down and updated again at power
up.
Displays the total time that the AC drive has been in the
Run Mode.
Reset the run time counter. The stored information will be
erased and a new registration period will start.
Displays the total time that the AC drive has been connected
to the mains supply. This timer cannot be reset.
Displays the total energy consumption since the last energy
reset [7331] took place.
NOTE: The shown percentages are absolute values
based on the full range/scale of the in- or output; so
related to either 0–10 V or 0–20 mA.
728
0rpm
IO B1
RE 000 DI100
Sby
Rem/Rem
72C
0rpm
VIO Status
00000000
Sby
Rem/Rem
731
Run Time
Unit:
hh:mm:ss (hours: minutes: seconds)
Range:
00: 00: 00–262143: 59: 59
7311
Reset RunTm
Default:
No
No
0
Yes
1
NOTE: After reset the setting automatically reverts to
“No”.
732
Mains Time
Unit:
hh:mm:ss (hours: minutes: seconds)
Range:
00: 00: 00–262143: 59: 59
733
Energy
Unit:
Wh (shows Wh, kWh, MWh or GWh)
Range:
0.0–1GWh,
Counter will restart at 0 after 1GWh
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......