182
CG Drives & Automation 01-7491-01r0
PT100_1_2_3 Temperature [71B]
Displays the actual PT100 temperature, for PT100 board 1.
PT100_4_5_6 Temperature [71C]
Displays the actual PT100 temperature, for PT100 board 2.
11.7.2
Frequency Inverter Status [721]
Indicates the overall status of the AC drive.
Fig. 148 AC drive status
Example: “A/Key/Rem/TL”
This means:
A:
Parameter Set A is active.
Key:
Reference value comes from the keyboard (CP).
Rem:
Run/Stop commands come from terminals 1-22.
TL: Torque
Limit
active.
Description of communication format.
Integer values and bits used.
71B
PT100 1,2,3
Unit:
°C
Resolution:
1°C
71C
PT100 4,5,6
Unit:
°C
Resolution:
1°C
721
0rpm
VSD Status
1/222/333/44
Sby
Rem/Rem
Display
position
Function
Status value
1
Parameter Set
A,B,C,D
222
Source of
reference value
Rem (remote)
Key (keyboard)
Com (Serial comm.)
Opt (option)
333
Source of Run/
Stop command
Rem (remote)
Key (keyboard)
Com (Serial comm.)
Opt (option)
44
Limit functions
- -No limit active
VL (Voltage Limit)
SL (Speed Limit)
CL (Current Limit)
TL (Torque Limit)
Bit
Integer representation
1 - 0
Active Parameter set, where
0=A, 1=B, 2=C, 3=D
4 - 2
Source of Reference control value, where
0=Rem, 1=Key, 2=Com, 3=Option
7 - 5
Source of Run/Stop/Reset command, where
0=Rem, 1=Key, 2=Com, 3=Option
13 - 8
Active limit functions, where
0=No limit, 1=VL, 2=SL, 3=CL, 4=TL
14
Inverter is in warning (A warning condition is
active)
15
Inverter is tripped (A Trip condition is active)
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......