144
Functional description
CG Drives & Automation 01-7491-01r0
If the speed of the pump reaches the upper band limit, the
next pump is started immediately without delay. If a start
delay is used this delay will be ignored. Range is between
0%, equalling max speed, and the set percentage for the
“UpperBand [397]”.
Fig. 121 Upper band limit.
If the speed of the pump reaches the lower band limit, the
'top' pump is stopped immediately without delay. If a stop
delay is used this delay will be ignored. Range is from 0%,
equalling min speed, to the set percentage for the “Lower
Band [398]”.
Fig. 122 Lower band limit
The settle start allows the process to settle after a pump is
switched on before the pump control continues. If an
additional pump is started D.O.L. (Direct On Line) or Y/
,
the flow or pressure can still fluctuate due to the 'rough'
start/stop method. This could cause unnecessary starting
and stopping of additional pumps.
During the Settle start:
•
PID controller is off.
•
The speed is kept at a fixed level after adding a pump.
39B
Upp Band Lim
Default:
0%
Range:
0 to Upper Band level. 0% (=max speed)
means that the Limit function is switched off.
(NG_50-PC-14_2)
Speed
Max
Min
Upper band
Start Delay [399]
Upper band
limit [39B]
next pump starts
immediately
Flow/Pressure
39C
Low Band Lim
Default:
0%
Range:
0 to Lower Band level. 0% (=min speed)
means that he Limit function is switched off.
39D
Settle Start
Default:
0 s
Range:
0-999 s
(NG_50-PC-15_2)
Speed
Max
Min
Lower band
Stop Delay [39A]
Lower band
limit [39C]
“top” pump stops
immediately
Flow/Pressure
Δ
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......