CG Drives & Automation 01-7491-01r0
Functional description
143
If the speed of the master drive comes into the upper band,
an additional drive will be added after a delay time that is set
in “Start delay [399]”.
Example
Max Speed = 1500 rpm
Min Speed = 300 rpm
Upper Band = 10%
Start delay will be activated:
Range = Max Speed to Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 1500–120 = 1380 rpm
Fig. 119 Upper band.
Lower Band [398]
If the speed of the master drive comes into the lower band
an additional drive will be stopped after a delay time. This
delay time is set in the parameter “Stop Delay [39A]”.
Example
Max Speed = 1500 rpm
Min Speed = 300 rpm
Lower Band = 10%
Stop delay will be activated:
Range = Max Speed - Min Speed = 1500–300 = 1200 rpm
10% of 1200 rpm = 120 rpm
Start level = 300 + 120 = 420 rpm
Fig. 120 Lower band.
This delay time must have elapsed before the next pump is
started. A delay time prevents the nervous switching of
pumps.
Stop Delay [39A]
This delay time must have elapsed before the 'top' pump is
stopped. A delay time prevents the nervous switching of
pumps.
397
Upper Band
Default:
10%
Range:
0-100% of total min speed to max speed
398
Lower Band
Default:
10%
Range:
0-100% of total min speed to max speed
(NG_50-PC-12_1)
Flow/Pressure
Speed
Max
Min
Upper band
next pump starts
Start Delay [399]
399
Start Delay
Default:
0 s
Range:
0-999 s
39A
Stop Delay
Default:
0 s
Range:
0-999 s
(NG_50-PC-13_1)
Speed
Max
Min
“top” pump stops
Lower band
Stop Delay [39A]
Flow/Pressure
Summary of Contents for FDU Series
Page 1: ...Emotron FDU 2 1 AC drive Instruction manual English Valid from software version 5 00...
Page 2: ......
Page 4: ......
Page 10: ...6 CG Drives Automation 01 7491 01r0...
Page 50: ...46 Installation CG Drives Automation 01 7491 01r0...
Page 60: ...56 Control Connections CG Drives Automation 01 7491 01r0...
Page 64: ...60 Getting Started CG Drives Automation 01 7491 01r0...
Page 84: ...80 EMC and standards CG Drives Automation 01 7491 01r0...
Page 195: ...CG Drives Automation 01 7491 01r0 191...
Page 196: ...192 CG Drives Automation 01 7491 01r0...
Page 204: ...200 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 7491 01r0...
Page 219: ...CG Drives Automation 01 7491 01r0 Technical Data 215...
Page 254: ...250 Menu List CG Drives Automation 01 7491 01r0...
Page 259: ......