3. Installation of Frequency Inverter
EM12 User’s Manual
20
Frequency inverter
Model
MCCB
(A)
Contactor
(A)
Cable of Input Side
Main Circuit
(mm2)
Cable of Output Side
Main Circuit
(mm2)
Cable of Control
Circuit
(mm2)
EM12- G3-132/P3-160
400
400
150
150
1.0
EM12- G3-160/P3-200
500
400
185
185
1.0
EM12- G3-200/P3-220
630
600
150*2
150*2
1.0
EM12- G3-220/P3-250
630
600
150*2
150*2
1.0
EM12- G3-250/P3-280
800
600
185*2
185*2
1.0
EM12- G3-280/P3-315
800
800
185*2
185*2
1.0
EM12- G3-315/P3-355
1000
800
150*3
150*3
1.0
EM12- G3-355/P3-400
1000
800
150*4
150*4
1.0
EM12- G3-400/P3-450
1200
1000
150*4
150*4
1.0
EM12-G3-450--
1200
1200
150*4
150*4
1.0
3.6 Removal and mounting of operating panel and cover
3.6.1 Removal and mounting of operating panel (keypad)
The operating panel of EM12 series Frequency inverter is a plug type, If you need to take it off when use or
maintenance, please make sure the gentle actions, or it is easy to damage the plug type connection terminals on
operating panel.
The removal and mounting of operating panel (keypad) is showed as Diagram3-3 and Diagram3-4:
Diagram 3-3 Removal of operating panel (keypad) Diagram 3-4 Mounting of operating panel (keypad)
3.6.2 Removal and Mounting of Frequency Inverter
The EM12 series frequency inverter below 22kw (380V) uses plastic case. The removal and mounting of upper
cover refers Diagram3-5. Please use tool to push the hooks on both side of lower cover.
Summary of Contents for EM12 Series
Page 5: ......