EM12 User’s Manual
Appendix II
129
Appendix II. Function Code Table
If A0-00 is set to a non-zero number, parameter protection is enabled. You must write in correct user password to
enter the menu.
To cancel the password protection function, enter with password and set A0-00 to 0.
The parameter menu under the user-defined parameter mode can directly enter without password.
Group “A” is frequency inverter system parameter. Group “b” is basic function parameters. Group “C” is
application parameter, Group “d” is control parameter, and Group “U” is monitoring function parameters.
The symbols in the function code table are described as follows:
"
☆
": The parameter can be modified when the frequency inverter is in stop or running state.
"
★
": The par
ameter cannot be modified when the frequency inverter is in running state.
"
●": The parameter is the actually measured value and cannot be modified.
"*": The parameter is factory parameter and can be modified only by the manufacturer.
Standard Function Parameters
Code
Parameter Name
Setting range
Default
Property
Group b0: Basic Function Parameters
b0-00 Motor type selection
0: AC asynchronous motor
1: Permanent magnetic synchronous motor
00
★
b0-01 Motor control mode
0: Sensor-less vector control (SVC)
1/2:V/F control
3: Closed-loop vector control (FVC)
2
★
b0-02 Command source selection
0: Keypad control (LED off)
1: Terminal control (LED on)
2: Communication control (LED blinking)
0
★
b0-03
Main frequency source X
selection
0: Digital setting (Preset frequency b0-12, UP/DOWN
modifiable, no-record after power off)
1: Digital setting (Preset frequency b0-12, UP/DOWN
modifiable, record after power off)
2: AI1
3: AI2
4: AI3
5: Pulse setting (HDI)
6: Multi-function
7:Built-in PLC
8: PID
9: Communication setting
10. Keypad Potentiometer
10
★
b0-04
Auxiliary frequency
source Y selection
The same as b0-03 (Main frequency source X selection)
0
★
b0-05
Selection of auxiliary
frequency Y range
0: Relative to maximum frequency
1: Relative to main frequency X
0
☆
b0-06
Range of auxiliary
frequency Y
0%~150%
100%
☆