EM12 User’s Manual
Appendix II
157
Code
Parameter Name
Setting range
Default
Property
d1-21
Maximum current of PM
field weakening
1%~300%
50%
☆
d1-22
PM Field weakening
automatic adjustment gain
100~500
100
☆
d1-23
PM Field weakening
integral multiple
2~10
2
☆
d1-24
Torque setting source in
torque control
0: Digital setting (d1-27)
1: AI1
2: AI2
3: AI3
4: Pulse setting (HDI)
5: Communication setting
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
Full range of values 1~7 corresponds to the digital
setting of d1-27.
0
☆
d1-26
Torque digital setting in
torque control
-200.0%~200.0%
100.0%
☆
d1-28
Forward maximum
frequency in torque control
0.00 Hz ~ maximum frequency(b0-13)
50.00 Hz
☆
d1-29
Reverse maximum
frequency in torque control
0.00 Hz ~ maximum frequency(b0-13)
50.00 Hz
☆
d1-30
Acceleration time in torque
control
0.00s~650.00s
0.00s
☆
Group d2: V/F Control Parameters
d2-00 V/F curve setting
0: Linear V/F
1: Multi-point V/F
2: Square V/F
3: 1.2-power V/F
4: 1.4-power V/F
6: 1.6-power V/F
8: 1.8-power V/F
10: V/F complete separation
11: V/F half separation
0
★
d2-01 Torque boost
0.0% ( torque auto-boost)
0.1%~30.0%
3.0%
★
d2-02
Cut-off frequency of
torque boost
0.0%~80.0%
Actual cut-off frequency= Motor rated
frequency*(d2-02)
50.0%
★
d2-03
Multi-point V/F frequency
1 (F1)
0.00 Hz ~ d2-05
0.00 Hz
☆
d2-04
Multi-point V/F voltage 1
(V1)
0.0%~100.0%
0.0%
☆
d2-05
Multi-point V/F frequency
2 (F2)
d2-03 to d2-07
0.00 Hz
☆
Summary of Contents for EM12 Series