EM12 User’s Manual
5. Description of Function Codes
49
K4
K3
K2
K1
Reference Setting
Corresponding Parameter
OFF
OFF
OFF
OFF
Reference 0
C1-00
OFF
OFF
OFF
ON
Reference 1
C1-01
OFF
OFF
ON
OFF
Reference 2
C1-02
OFF
OFF
ON
ON
Reference 3
C1-03
OFF
ON
OFF
OFF
Reference 4
C1-04
OFF
ON
OFF
ON
Reference 5
C1-05
OFF
ON
ON
OFF
Reference 6
C1-06
OFF
ON
ON
ON
Reference 7
C1-07
ON
OFF
OFF
OFF
Reference 8
C1-08
ON
OFF
OFF
ON
Reference 9
C1-09
ON
OFF
ON
OFF
Reference 10
C1-10
ON
OFF
ON
ON
Reference 11
C1-11
ON
ON
OFF
OFF
Reference 12
C1-12
ON
ON
OFF
ON
Reference 13
C1-13
ON
ON
ON
OFF
Reference 14
C1-14
ON
ON
ON
ON
Reference 15
C1-15
If the frequency source is multi-function, the value 100% of C1-00~ C1-15 corresponds to the value of b0-13
(Maximum frequency).
Besides as the multi-speed function, the multi-function can be also used as the PID setting source or the voltage
source for V/F separation, satisfying the requirement on switchover of different setting values.
Table 5-2 Function description of Acceleration/Deceleration time selection terminals
Terminal 2
Terminal 1
Acceleration/Deceleration Time
Corresponding
OFF
OFF
Acceleration/Deceleration time 1
b0-21, b0-22
OFF
ON
Acceleration/Deceleration time 2
b2-03, b2-04
ON
OFF
Acceleration/Deceleration time 3
b2-05, b2-06
ON
ON
Acceleration/Deceleration time 4
b2-07, b2-08
Table 5-3 Function description of motor selection terminals
Terminal 1
Selected Motor
Corresponding Parameters
OFF
Motor 1
Group d0, Group d1, Group d2
ON
Motor 2
Group d3, Group d4, Group d5
b3-12
DI filter time
Default
0.010s
Setting Range
0.000s~1.000s
It is used to set the software filter time of DI terminal status. If DI terminals are liable to interference and may cause
malfunction, increase the value of this parameter to enhance the anti-interference capability. However, increase of DI
filter time will slow down the response of DI terminals.
b3-13
Terminal command mode
Default
0
Setting
Range
0
Two-line mode 1
1
Two-line mode 2
3
Three-line mode 1
4
Three-line mode 2
This parameter is used to set the mode in which the frequency inverter is controlled by external terminals. The
following uses DI1, DI2 and DI3 among DI1 to DI12 as an example, with allocating functions of DI1, DI2 and DI3 by
setting b3-00 to b3-02.
0: Two-line mode 1
It is the most commonly used two-line mode, in which the forward/reverse rotation of the motor is decided by DI1
and DI2. The parameters are set as below: