EM12 User’s Manual
5. Description of Function Codes
51
Diagram 5-12 Setting of three-line mode 1
As shown in the preceding figure, if SB1 is ON, the frequency inverter instructs forward rotation when Sb2 is pressed
to be ON, and instructs reverse rotation when SB3 is pressed to be ON. The frequency inverter stops immediately
after SB1 becomes OFF. During normal startup and running, SB1 must remain ON. The frequency inverter's running
state is determined by the final actions on SB1, SB2 and SB3.
3: Three-line mode 2
In this mode, DI3 is RUN enabled terminal. The RUN command is given by DI1 and the direction is decided by DI2.
The parameters are set as below:
Code
Name
Value
Function Description
b3-13
Terminal command mode
3
Three-line 2
b3-00
DI1 function selection
1
RUN enabled
b3-01
DI2 function selection
2
Forward or reverse
b3-02
DI3 function selection
3
Three-line control
Diagram 5-13 Setting of three-line mode 2
As shown in the preceding figure, if SB1 is ON, the frequency inverter starts running when SB2 is pressed to be ON;
the frequency inverter instructs forward rotation when K is OFF and instructs reverse rotation when K is ON. The
Frequency inverter stops immediately after SB1 becomes OFF. During normal startup and running, SB1 must remain
ON
,
SB2 is effective immediately after
ON action.
b3-14
Rate of UP/DOWN terminal
Default
1.000 Hz/s
Setting Range
0.001Hz/s~65.535 Hz/s
It is used to adjust the ratio of changing of frequency for per second when the frequency is adjusted by means of
terminal UP/DOWN.
1.
If b0-11 (Frequency reference resolution) is 2, the setting range is 0.001Hz/s~65.535 Hz/s.
2.
If b0-11 (Frequency reference resolution) is 1, the setting range is 0.01Hz/s~655.35 Hz/s.