EM12 User’s Manual
5. Description of Function Codes
91
C3-01
Full scale maximum pressure (Mpa)
Default
1.000Mpa
Setting Range
0.000~60.000Mpa
C3-02
Pressure lower limit (Mpa)
Default
0.001Mpa
Setting Range
0.000~60.000Mpa
C3-03
Pressure upper limit (Mpa)
Default
1.000Mpa
Setting Range
0.000~60.000Mpa
C3-04
Sleep wakeup pressure (Mpa)
Default
0.001Mpa
Setting Range
0.000~60.000Mpa
C3-05
Sleep pressure (Mpa)
Default
1.000Mpa
Setting Range
0.000~60.000Mpa
C3-06
The lasting time of feedback pressure is more than actual pressure
Default
10s
Setting Range
0~250s
C3-07
Sleep frequency
Default
20.00HZ
Setting Range
0.00~maximum frequency
C3-08
The lasting time of frequency is less than sleep pressure
Default
10s
Setting Range
0~250s
C3-09
Sleep selection
Default
0
Setting
Range
0
Frequency sleep available
1
Pressure selection available
5.18 Group d0: Motor 1 Parameters
d0-00
Rated motor power
Default
Model dependent
Setting Range
0.1kw~1000.0 kW
d0-01
Rated motor voltage
Default
Model dependent
Setting Range
1V~2000 V
d0-02
Rated motor current
Default
Model dependent
Setting Range
0.01A~655.35 A (Frequency inverter power
≤55 kW)
0.1A~6553.5 A (Frequency inverter power
≥75 kW)
d0-03
Rated motor frequency
Default
50.00Hz
Setting Range
0.01 Hz~ maximum frequency
d0-04
Rated motor rotational speed
Default
Model dependent
Setting Range
1rpm~65535rpm
Set the parameters according to the motor nameplate no matter whether V/F control or vector control is adopted.
To achieve better V/F or vector control performance, motor auto-tuning is required. The motor auto-tuning
accuracy depends on the correct setting of motor nameplate parameters.
d0-05
Stator resistance (asynchronous motor)
Default
Model dependent
Setting Range
0.001
Ω ~65.535 Ω (frequency inverter power≤ 55 kW)
0.0001
Ω ~6.5535 Ω (frequency inverter power ≥75 kW)
d0-06
Rotor resistance (asynchronous motor)
Default
Model dependent
Setting Range
0.001
Ω ~65.535 Ω (Frequency inverter power≤ 55 kW)
0.0001
Ω ~6.5535 Ω (frequency inverter power ≥75 kW)
d0-07
Leakage inductive reactance (asynchronous motor)
Default
Model dependent
Setting Range
0.01mH~655.35 mH (frequency inverter power
≤ 55 kW)
0.001mH~65.535 mH (frequency inverter power
≥75 kW)
Summary of Contents for EM12 Series