4.
Use the arrow keys to change the setting. Press
ENTER
to save.
The screen displays the HOLD prompt.
5.
Use the arrow keys to change the setting to the output desired when the transmitter
is in hold mode.
The range is 3.80 to 22.0 mA. If 00.00 is selected, the transmitter will hold the
output value.
6.
Press
ENTER
to save.
NOTICE
The hold setting overrides the fault setting.
The screen displays the FAULT prompt.
7.
Use the arrow keys to change the setting to the output desired when the transmitter
is in fault mode.
The range is 3.80 to 22.0 mA. If 00.00 is selected, the transmitter will hold the
output value.
8.
Press
ENTER
to save.
The screen displays the DPN prompt.
Programming - basics
34
Rosemount 5081
Summary of Contents for Rosemount5081
Page 4: ......
Page 10: ...Contents vi Rosemount 5081 ...
Page 12: ...Startup procedure 2 Rosemount 5081 ...
Page 23: ...Mounting 5081 on a pipe Figure 3 2 Installation Instruction Manual 13 ...
Page 24: ...Installation 14 Rosemount 5081 ...
Page 28: ...Wiring 18 Rosemount 5081 ...
Page 50: ...Programming basics 40 Rosemount 5081 ...
Page 130: ...Diagnostics and troubleshooting 120 Rosemount 5081 ...
Page 136: ...Digital communications 126 Rosemount 5081 ...
Page 140: ...Engineering drawings 130 Rosemount 5081 ...
Page 141: ...Engineering drawings Instruction Manual 131 ...
Page 142: ...Engineering drawings 132 Rosemount 5081 ...
Page 143: ...Engineering drawings Instruction Manual 133 ...
Page 144: ...Engineering drawings 134 Rosemount 5081 ...
Page 145: ...Engineering drawings Instruction Manual 135 ...
Page 146: ...Engineering drawings 136 Rosemount 5081 ...
Page 151: ...EU Declarations of Conformity 138 Rosemount 5081 ...