7
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
10. Set the Device Address to the 3D Solids Scanner's SCADA ID. This first serial port (P01) can be
configured to communicate with the 5708 3DMultiVision server. Select
Add
to add the IP definition
of the device.
Note
The 3DVision is assigning SCADA ID to the vessel regardless to the number of scanners configured in the vessel. this
is done to allow the DeltaV to get the complete data from of the vessel and not independent scanner.
11. Enter the
IP Address
of the DeltaV Application Station - the station running the 3DMultiVision Server.
12. In the
Protocol
list, select
RTU via TCP
.
13. In the
Port
box, type
12345
.
Figure 1-3. Configure the IP Definition for the Device
A. 3DMultiVision PC goes here
14. If a multidrop connection is desired, then each scanner should be linked with a device instance
under the associated virtual serial port. Repeat steps
to add each physical device; choose the
appropriate Device Address to match the address of the physical devices.
Note
That each scanner should be configured with a different polling address.