Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
Figure 1-8. Expression in CALC Block Control Strategy for Floating Points
4.
For the parameter SN (Serial Number), the byte order must be swapped and converted from binary
to long integer. A control strategy with the configuration shown in
was used.
Figure 1-9. Control Strategy for Long Integers