Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
3.0
Network setup
To be able to run 5708 3DMultiVision software simultaneously with DeltaV, set up the network as
follows:
1.
Setup a network switch connected to the DeltaV controller, the DeltaV ProPlus station, and the
DeltaV Application Station. The DeltaV Application Station will be the station running the
3DMultiVision software.
2.
Setup another, separate network switch connected to the VIM card, the DeltaV Application Station
running 3DMultiVision, and the 3D Solids Scanner.
Note
The 3D Solids Scanner uses a serial communication link to the network. An RS485 to TCP/IP converter is required to
connect the device to the network switch. An RS485 to USB converter is required to connect the device to the
application station.
Figure 1-1. Network Diagram
A. 3DMultiVision
B. DeltaV
ProPlus
C. DeltaV
Operator
Station
D. VIMNet
Explorer
(Optional)
E. Multiple 3D Solids Scanners