21
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
b. On the
DeltaV
tab, in the
DeltaV data type
list, select the appropriate data type for the values
which are to be retrieved. See figures on
Example setup for dataset constructed to read the
Example setup for dataset constructed to read the “Tag Name”
below.
DeltaV data type
: Enter the appropriate data type for the values which are to be retrieved.
i. Select
16 bit unit with status
: use for the first 12 parameters in registers 40001-40024.
It will be referred to as Dataset1.
ii. Select
String with status
: use for the ‘Tag Name’ parameter in registers 40025-40026. It
will be referred as Dataset2.
c. On the
PLC
tab use the following settings:
i.
PLC data type
:
holding registers
(apply for both
Datasets properties
)
ii.
PLC register offset
: Enter the start address. For example, if the first value should be ‘Avg
Distance’, enter
0
. If the first value should be Avg. Level, enter
16
.
iii.
Number of values
: Enter the desired number of values to read. Note that to read each
parameter (Avg. Distance, Min Distance, Max Distance, etc.), two values are required.
Example setup for dataset constructed to read the first 12 parameters
Example setup for dataset constructed to read the “Tag Name” parameter
Note
The Dataset Tag can be modified to facilitate the data management.
DeltaV tab. Setup DeltaV data type as 16 bit unit w/Status.
PLC tab. Setup the PLC data type as holding registers, PLC
register offset as 0, and Number of values as 24.
DeltaV tab. Setup DeltaV data type as String w/Status.
PLC tab. Setup the PLC data type as holding registers, PLC
register offset as 24, and Number of values as 2.