5
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
6.
In a multi-scanner system, where a vessel in the 3DVision is configured with multiple scanners it is
possible to view the vessel's data on the SCADA, use the vessel ID to set the connection between the
DeltaV to the 3DVision.
The Vessel ID can be seen in the hardware inventory table: in 3DVision go to
Tools > Reports >
Hardware Inventory Table
. The Vessel ID appears in the right most column under the SCADA ID
header.
3.2
Configuring VIMNet
1.
Open VIMNet Explorer on the DeltaV Application Station.
2.
Right-click on
I/O Net
and select
New Controller
. This will open a prompt for the name of the new
controller.
3.
Type the name of the new controller. The name of the new controller in VIMNet must match the
name of the controller in DeltaV.
4.
Right-click the controller that was added to VIMNet in step
, and select
New IO VIM
to open the
Add Modbus/TCP Virtual I/O Module
window and begin commissioning the VIM.