19
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
10. On the
Communications
tab, use the following settings:
Port type:
RS422/RS485 half duplex
Baud rate:
115200
Parity:
even
Data bits:
8
Stop bits:
1
Note
Communication parameters in step
were taken from the manual “Different Ways of Connecting to 3D Solids
Scanner II Version 3.0”. Refer to the Rosemount 5708 Series 3D Solids Scanner
to confirm these
parameters.
11. Select the port of the serial card (PO1 or PO2) where the 3D Solids Scanner is connected and where
the communication parameters were set in the above steps.
12. Right-click and select
New Serial device
.
13. Set the device address to match the address of the physical 3D Solids Scanner connected to the
serial card. The Device Address will be the 3D Solids Scanner’s Polling A 1.
14. If a multidrop connection is desired, each scanner must be linked with a device instance under the
associated serial port. Repeat steps
for the second device. Set the address of the
devices to match the address of the physical devices connected to the serial card. Note that each
scanner should be configured with a different polling address.