13
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
c.
On the
PLC
tab, use the following settings:
Device data type
3
Data start address: enter the start address. For example, if the first value should be 'Avg
Distance', enter
0
. If the first value should be Avg Level, enter
16
.
Number of values: enter the desired number of values to read. Note that reading the
'Tag Name' requires 2 values.
d.
On the
Special data
tab, use the following settings:
No changes need to be made to Special data 1, Special data 3, Special data 4, or Special
data 5 - the values should all remain 0.
Special data 2 should be set to
1
only on the dataset to retrieve the 'Tag Name'
parameter. For all other datasets the value should remain
0
.
For example, to configure all 13 parameters, construct three datasets with the following
parameters:
Table 1-2. Example Configurations
Parameter
Dataset 1
Dataset 2
Dataset 3
Dataset 4
DeltaV data type
Floating point
with status
32-bit unit
with status
String with
status
16- bit uint
with status
Data start address 0
22
24
9989
Number of values
11
1
2
1
Special data 2
0
0
1
0