Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2.
Command line breakdown:
Testing
1.
Once the script is entered, close
Microsoft Visual Basic,
save and close the graphic file.
2.
Press the
Run
button
in DeltaV Operate Configure and open the desired operator graphic.
3.
Select the new button
and the
3D image
window will open and the image will load. You will be able
to maneuver the image with the mouse.
Command Line
Definition
\\usrtc-smartlab1
Name of server
C
Shared drive that contains 3DVision Server software program files
\program files
(x86)\3DVisionEmrsn\binclient\bin\
Path to software
visualvision3dviewer .exe
Image display program. There must be a space after .exe!
\\usrtc-smartlab1\c\3dvision
Location of image file as entered in 3DVision software server but in the
format \\server\share\folder path
1
image file name, same as SCADA ID
vbNormalFocus
Causes the image window to display in the foreground.
taskkill.exe /im
visualvision3dviewer.exe
Ends the image program when it is called again if the operator does not
close it. The prevents multiple windows from being open in the
background where the operator cannot get to them to close them.