12
Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
b. On the
DeltaV
tab, in the DeltaV data type list, select the appropriate data type for the
values which are to be retrieved.
i. Select
32-bit unit with status
if using the “S/N” parameter in registers 40023-40024.
ii. Select
Floating point with status
if using parameters in registers 40001-40022.
iii. Select
String with status
if using the “Tag Name” parameter in registers 40025-40026.
iv. Select
16-bit uint
with status
if using 3D data in register 49990. This register does not
deliver data, but polling this register is required for creation of the 3D data files.
Table 1-1. Registers
Number
Register number
Parameter
Units
Type
1
40001 and 40002
Avg. distance
m
Floating point
2
40003 and 40004
Min distance
m
Floating point
3
40005 and 40006
Max distance
m
Floating point
4
40007 and 40008
Volume
% (*1000)
Floating point
5
40009 and 40010
4-20mA
mA
Floating point
6
40011 and 40012
SNR
dB
Floating point
7
40013 and 40014
Temperature
°C
Floating point
8
40015 and 40016
Temperature
°F
Floating point
9
40017 and 40018
Avg. level
m
Floating point
10
40019 and 40020
Bulk density
g/cm^3
Floating point
11
40021 and 40022
Mass
customer unit
Floating point
12
40023 and 40024
S/N
number
Long integer
13
40025 and 40026
Tag name
First 4 chars
Integer
14
49990
3D
N/A
Floating point