Manual Supplement
00809-0300-4570, Rev BA
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
2016
Rosemount 5708 Series 3D Solids Scanner Integration with DeltaV
5.
The IP Address of the VIM can be set to any available IP on the network; the availability of an IP can
be checked using the Ping function at the bottom left of the pop up window. Select
OK
when all of
the parameters are set correctly. This will create a new VIM connection for the controller emulating
four serial I/O cards.
Figure 1-2. Set the VIM Properties
A. Any available IP will work
B. Subnet mask set to match network
C. Check IP availability here
6.
Right-click the
VIM
which was just added and select
Commission
. A list will populate with
Decommissioned VIMs on the network.
7.
Select the desired VIM to be commissioned (an
Identify VIM
function is available in the bottom right
of the window).
8.
Check that the
IP Address
field matches the available IP address set in
, and select
OK
.
9.
Expand the VIM icon to see the emulated serial cards, numbered 57-60. To begin the setup of the
VIM, expand one of the cards and right-click on one of the serial ports assigned to the card. Select
Add Device
to open the
Device Properties
window.