September 2016
Reference Manual
00809-0100-4022, Rev GA
60
Markings: Intrinsically Safe for use in Class I, Division
1, Groups A, B, C, and D; Temperature
Code T3C (–50 °C to 70 °C); Intrinsically
Safe for use in Class I, Zone 0 Ex ia IIC T4
(–50 °C to 70 °C) when connected in
accordance with Rosemount drawing
04620-5005; Enclosure Type 4X; For
entity parameters see control drawing
04620-5005
B.2.2 Europe
E1
ATEX Flameproof
Certificate: KEMA02ATEX2231X
Standards: EN60079-0:2006; EN60079-1:2007;
EN60079-26:2007
Markings:
II 1/2 G Ex d IIC T6 (–40 °C
≤
T
a
≤
+70 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm.
Installation, maintenance, and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. The Rosemount 4600 Pressure Transmitter is
provided with a permanently connected
unterminated cable. The free end of the cable shall be
connected using a suitable junction box, e.g. in type
of protection flameproof enclosure “d” or increased
safety “e”.
I1
ATEX Intrinsic Safety
Certificate: Baseefa03ATEX0114X
Standards: EN60079-0:2012+A11:2013,
EN60079-11:2012
Markings:
II 1 G Ex ia IIC T4 Ga (–40 °C
≤
T
a
≤
+70 °C)
Special Condition for Safe Use (X):
1. The equipment with the Transient Protection (T1)
option is not capable of withstanding the 500 V
insulation test required by Clause 6.3.13 of
EN60079-11:2012. This must be taken into account
when installing the equipment.
N1
ATEX Type n
Certificate: Baseefa03ATEX0115X
Standards: EN60079-0:2012+A11:2013,
EN60079-15:2010
Markings:
II 3G Ex nA IIC T5 Gc (–40 °C
≤
T
a
≤
+70 °C)
U
i
= 42.4V
Special Condition for Safe Use (X):
1. The equipment with the Transient Protection (T1)
option is not capable of withstanding the 500 V
insulation test required by Clause 6.5.1 of
EN60079-15:2010. This must be taken into account
when installing the equipment.
ND
ATEX Dust
Certificate: KEMA02ATEX2231X
Standards: EN60079-0:2006, EN60079-26:2007,
EN61241-0:2006, EN61241-1:2004 +
C1:2006
Markings:
II 1 D Ex tD A20 T85 °C (–40 °C
≤
T
a
≤
+70 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm.
Installation, maintenance, and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. The Rosemount 4600 is provided with a permanently
connected unterminated cable. The free end of the
cable shall be connected using a suitable junction
box, e.g. in type of protection flameproof enclosure
“d” or increased safety “e”.
B.2.3 Brazil
E2
INMETRO Flameproof
Certificate: UL-BR 15.0509X
Standards: ABNT NBR IEC 60079-0, ABNT NBR IEC
60079-1, ABNT NBR IEC 60079-26
Markings: Ex d IIC Ga/Gb, T6(–60 °C
≤
T
a
≤
+70 °C),
T5/T4(–60 °C
≤
T
a
≤
+80 °C)
Special Condition for Safe Use (X):
1. This device contains a thin wall diaphragm.
Installation, maintenance and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail in order to assure safety during its
expected lifetime.
Input parameters
HART
Voltage U
i
30 V
Current I
i
200 mA
Power P
i
1.0 W
Capacitance C
i
35 nF
Inductance L
i
390
μ
H