14
Reference Manual
00809-0100-4022, Rev GA
Configuration
September 2016
Configuration
AMS Device Manger
1.
Right click on the device, select
Device Configuration
,
2.
Select
Alarm/Saturation Levels
,
3.
Select
Alarm Levels
from the menu
.
4.
Select
Next
after setting the control loop to manual.
5.
Select
Next
after acknowledging the current alarm levels.
6.
Select the desired alarm settings:
NAMUR
,
Rosemount
,
Other
7.
If
Other
is selected, enter desired
HI Value
and
LO Value
custom values.
8.
Select
Next
to acknowledge new alarm levels.
9.
Select
Next
to acknowledge the loop can be returned to automatic control.
10.
Select
Finish
to acknowledge the method is complete.
11.
Right click on the device, select
Device Configuration
, then select
Alarm/Saturation Levels
, then
Alarm Levels
from the menu
.
12.
Select
Saturation Levels
.
13.
Repeat
to configure saturation levels.
2.8.3
Alarm and saturation levels for burst mode
Transmitters set to burst mode handle saturation and alarm conditions differently.
Alarm conditions
Analog output switches to alarm value
Primary variable is burst with a status bit set
Percent of range follows primary variable
Temperature is burst with a status bit set
Saturation
Analog output switches to saturation value
Primary variable is burst normally
Temperature is burst normally