Configuration
September 2016
Configuration
Field Communicator
The process variable menu displays the following process variables:
Pressure
Percent of range
Analog output
Sensor temperature
Note
Regardless of the range points, the Rosemount 4600 will measure and report all readings
within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to
0 and 1,000 psi, and the transmitter detects a pressure of 2,500 psi, it digitally outputs the
2,500 psi reading and a 250% of span reading. However, there may be up to ±5.0% error
associated with output outside of the range points.
AMS Device Manger
Right click on the device and select
Process Variables...
from the menu.The process
variable screen displays the following process variables:
Pressure
Percent of range
Analog output
Sensor temperature
2.6.2
Sensor temperature
The Rosemount 4600 contains a temperature sensor near the pressure sensor in the
transmitter. When reading this temperature, keep in mind this is not an accurate indicator
of process temperature.
Field Communicator
Enter the Fast Key sequence below
Sensor Temperature
to view the sensor temperature
reading.
AMS Device Manger
Right click on the device and select
Process Variables...
from the menu.
Snsr Temp
is the
sensor temperature reading.
Fast Keys
1, 1, 4