Configuration
September 2016
Configuration
Figure 2-1. Bench Wiring (4–20 mA)
2.4
Field Communicator
The following menu indicates Fast Key sequences for common functions. For full Field
Communicator menu tree see
A. Rosemount 4600
B. R
L
> 250 ohm
C. Power supply
D. Current meter
E. Field Communicator
Function
HART Fast Key Sequence
Alarm Level Config.
1, 4, 2, 7, 7
Alarm and Saturation Levels
1, 4, 2, 7
Analog Output Alarm Direction
1, 4, 2, 7, 6
Analog Output Trim
1, 2, 3, 2
Burst Mode On/Off
1, 4, 3, 3, 3
Burst Options
1, 4, 3, 3, 4
Damping
1, 3, 6
Date
1, 3, 4, 1
Descriptor
1, 3, 4, 2
Digital To Analog Trim (4-20 mA Output)
1, 2, 3, 2, 1
Field Device Information
1, 4, 4, 1
Loop Test
1, 2, 2
Lower Sensor Trim
1, 2, 3, 3, 1
Message
1, 3, 4, 3
Number of Requested Preambles
1, 4, 3, 3, 2
Pressure Alert Config.
1, 4, 3, 4, 3
B
D
C
A
E