21
Reference Manual
00809-0100-4022, Rev GA
Configuration
September 2016
Configuration
2.10.2
Burst mode
When configured for burst mode, the Rosemount 4600 provides faster digital communication
from the transmitter to the control system by eliminating the time required for the control
system to request information from the transmitter. Burst mode is compatible with the analog
signal. Because the HART protocol features simultaneous digital and analog data transmission,
the analog value can drive other equipment in the loop while the control system is receiving the
digital information. Burst mode applies only to the transmission of dynamic data (pressure and
temperature in engineering units, pressure in percent of range, and/or analog output), and does
not affect the way other transmitter data is accessed.
Access to information other than dynamic transmitter data is obtained through the normal
poll/response method of HART communication. A Field Communicator, AMS Device Manger or
the control system may request any of the information that is normally available while the
transmitter is in burst mode. Between each message sent by the transmitter, a short pause
allows the Field communicator, AMS Device Manger or a control system to initiate a request.
The transmitter will receive the request, process the response message, and then continue
“bursting” the data approximately three times per second.
Field Communicator
To configure the transmitter for burst mode, perform the following step:
1.
From the
HOME
screen, enter the Fast Key sequence below
Burst Mode
.
AMS Device Manger
Right click on the device and select
Configuration Properties
from the menu.
1.
In the
HART
tab, use the drop down menu to select
Burst Mode ON
or
OFF
. For
Burst
option
select the desired properties from the drop down menu. Burst options are as
follows:
PV
% range/current
Process vars/crnt
Process variables
2.
After selecting options, select
Apply
.
3.
An
Apply Parameter Modification
screen appears, enter desired information and select
OK
.
4.
After carefully reading the warning provided, select
OK
.
Fast Keys
1, 4, 3, 3, 3
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China