41
Reference Manual
00809-0100-4022, Rev GA
September 2016
4.3.1
Zero Trim
Note
The transmitter must be within three percent of the span away from zero (for zero-based
spans) in order to calibrate with zero trim function. If the zero reading is not within three
percent of the true zero, the transmitter will require iterative trims to move the zero within
trimmable range.
Field Communicator
Calibrate the sensor with a Field Communicator using the zero trim function as follows:
1.
Vent the transmitter and attach a Field Communicator to the measurement loop.
2.
From the
Home
screen, follow the Fast Key sequence shown.
3.
Follow the commands provided by the Field Communicator to complete the zero
trim adjustment.
AMS Device Manger
1.
Right click on the device and select
Calibrate
, Select
Zero trim
from the menu
.
2.
Select
Next
after setting the control loop to manual.
3.
Select
Next
to acknowledge warning.
4.
Select
Next
after applying appropriate pressure to sensor.
5.
Select
Next
to acknowledge the loop can be returned to automatic control.
6.
Select
Finish
to acknowledge the method is complete.
Fast Keys
1, 2, 3, 3, 1