18
Reference Manual
00809-0100-4022, Rev GA
Configuration
September 2016
Configuration
AMS Device Manger
1.
Right click on the device and select
Diagnostics and Test
then
Loop test
from the
menu.
2.
Select
Next
after setting the control loop to manual.
3.
Select desired analog output level. Select
Next
.
4.
Select
Next
to acknowledge output being set to desired level.
5.
Check the reference meter installed in the test loop to verify that it displays the
commanded output value.
a.
If the values match, the transmitter and the loop are configured and functioning
properly.
b. If the values do not match, the current meter may be attached to the wrong loop, there
may be a fault in the wiring, the transmitter may require an output trim, or the
reference meter may be malfunctioning.
After completing the test procedure, the display returns to the loop test screen to select
another output value or to end loop testing.
6.
Select
End
and select
Next
to end loop testing.
7.
Select
Next
to acknowledge the loop can be returned to automatic control.
8.
Select
Finish
to acknowledge the method is complete.
2.10
Advanced functions for HART protocol
2.10.1
Saving, recalling, and cloning configuration data
Use the cloning feature of the Field Communicator or the AMS Device Manger “User
Configuration” feature to configure several Rosemount 4600 Transmitter similarly. Cloning
involves configuring a transmitter, saving the configuration data, then sending a copy of the
data to a separate transmitter. Several possible procedures exist when saving, recalling, and
cloning configuration data. For complete instructions refer to the Field Communicator
or AMS online guides. One common method is as follows:
Note
Do not clone an absolute pressure transmitter with sealed gauge pressure configuration data.
Do not clone a sealed gauge pressure transmitter with absolute pressure data.
Fast Keys
left arrow, 1, 2