13
Reference Manual
00809-0100-4022, Rev GA
Configuration
September 2016
Configuration
Failure mode alarm and saturation levels can be configured using a Field Communicator or
AMS Device Manager, see
“Alarm and saturation level configuration” on page 13
. Per
, custom alarm and saturation levels can be configured between 3.6 mA and
3.9 mA for low values and between 20.1 mA and 23 mA for high values. The following
limitations exist for custom levels:
Low alarm level must be less than the low saturation level
High alarm level must be higher than the high saturation level
High saturation level must not exceed 21.5 mA
Alarm and saturation levels must be separated by at least 0.1 mA
The Field Communicator or AMS Device Manager will provide an error message if a
configuration rule is violated.
2.8.2
Alarm and saturation level configuration
To configure alarm and saturation levels with a Field Communicator or AMS Device Manager
perform the following procedure:
Field Communicator
1.
From the
HOME
screen, follow the Fast Key sequence under Alarm and Saturation
Levels.
2.
Select
7, Config. Alarm Level
to configure alarm levels.
3.
Select
OK
after setting the control loop to manual.
4.
Select
OK
to acknowledge current settings.
5.
Select desired setting, if
OTHER
is selected, enter HI and LO custom values.
6.
Select
OK
to acknowledge the loop can be returned to automatic control.
7.
Select
8, Config. Sat. Levels
to configure saturation levels.
8.
Repeat steps
to configure saturation levels.
Fast Keys
1, 4, 2, 7