Reference Manual
00809-0100-4022, Rev GA
September 2016
AMS Device Manger
Right click on the device and choose
Calibrate
then
Scaled D/A trim
from the menu
.
1.
Select
Next
after setting the control loop to manual.
2.
Select
Change
to change scale
, select
Next
.
3.
Enter
Set scale-Lo output value
, select
Next
.
4.
Enter
Set scale-Hi output value
, select
Next
.
5.
Select
Next
to proceed with Trim.
6.
Select
Next
after connecting the reference meter.
7.
Select
Next
at the
Setting fld dev output to 4 mA
screen.
8.
Record the actual value from the reference meter, and enter it at the
Enter meter
value
screen and select
Next
.
9.
Select
Yes
, if the reference meter value equals the transmitter output value, or
No
if
it does not. Select
Next
.
a.
If
Yes
b. If
No
.
10.
Select
Next
at the
Setting fld dev output to 20 mA
screen.
11.
Repeat steps
until the reference meter equals the transmitter output value.
12.
Select
Next
to acknowledge the loop can be returned to automatic control.
13.
Select
Finish
to acknowledge the method is complete.