19
Reference Manual
00809-0100-4022, Rev GA
Configuration
September 2016
Configuration
Field Communicator
1.
Confirm and apply configuration changes to the first transmitter.
Note
If transmitter configuration has not been modified, “SAVE” option in
will be disabled.
2.
Save the configuration data:
a.
Select
SAVE
from the bottom of the Field Communicator screen.
b. Select to save your configuration in either the
“Internal Flash”
(default) or the
“Configuration EM”
(Configuration Expansion Module).
c.
Enter the name for this configuration file. The default name is the transmitter tag
number.
d. Select
SAVE
.
3.
Power the receiving transmitter and connect with Field Communicator.
4.
Access the HART Application menu by pressing the
LEFT ARROW
from the
HOME/ONLINE
screen.
5.
Locate the saved transmitter configuration file.
a.
Select
Offline
b. Select
Saved Configuration
c.
Select either
Internal Flash Contents
or
Configuration EM Content
depending on
where the configuration was stored per
.
6.
Use the
DOWN ARROW
to scroll through the list of configurations in the memory
module, and use the
RIGHT ARROW
to select and retrieve the desired
configuration.
7.
Select
Send
to transfer the configuration to the receiving transmitter.
8.
Select
OK
after the control loop is set to manual.
9.
After the configuration has been sent, select
OK
to acknowledge that the loop can
be returned to automatic control. When finished, the Field Communicator informs
you of the status. Repeat
through
to configure another transmitter.
Note
The transmitter receiving cloned data must have the same software version (or later) as the
original transmitter.