Reference Manual
00809-0100-4140, Rev AA
January 2017
Note
A
Restore Site Calibration
command becomes available afterwards. For a Field
Communicator, use fast key sequence 3, 4, 3, 2, 2.
To restore the factory calibration (AMS Device Manager)
1.
Right click on the device and select
Service Tools
.
2.
Select
Maintenance
, and then select the
Calibrate Sensor
tab.
3.
Click on the Restore Factory Calibration
button.
4.
Follow on-screen instructions to restore the calibration.
Note
When messages about the loop appear, take appropriate safe action.
See
“Configuration basics” on page 10
for further information.
Note
A
Restore Site Calibration
command becomes available afterwards. For the AMS Device
Manager, use the Restore Site Calibration button on the
Calibrate Sensor
tab.
To restore the factory calibration (LOI)
1.
Press any LOI button to activate the menu.
(See
for assistance with using the LOI buttons).
2.
Scroll down (
) and then select
EXTENDED MENU
(
).
3.
Select
CALIBRATE
(
).
4.
Scroll down (
) and then select
PARAMETR RECALL
.
5.
Select
DRY RECALL
(
).
6.
Follow on-screen instructions to restore the calibration.
Note
When messages about the loop appear, take appropriate safe action and select “
”.
See
“Configuration basics” on page 10
for further information.
Note
A
Restore Site Calibration
command becomes available afterwards.
Summary of Contents for Rosemount 2140
Page 2: ......
Page 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Page 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Page 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Page 143: ......