19
Reference Manual
00809-0100-4140, Rev AA
January 2017
To change or view the media density (LOI)
1.
Press any LOI button to activate the menu.
(See
for assistance with using the LOI buttons).
2.
Scroll down (
) and then select
EXTENDED MENU
(
).
3.
Scroll down (
) and then select
MEDIA
(
).
4.
Select
DENSITY
(
).
5.
Follow on-screen instructions to select an option that is closest to the process
medium density range.
Note
When messages about the loop appear, take appropriate safe action and select “
”.
See
“Configuration basics” on page 10
for further information.
2.8.4
Media learn
Versions of the Rosemount 2140 and Rosemount 2140:SIS with the Extended Features
Package (EFP) can use the
Media Learn
function.
Media Learn makes configuring the
Media Density
variable (
) even easier.
This procedure requires the fork tines to be fully immersed in the process medium for a
short period to gather the frequency data, calculate the liquid density, and then auto-select
the option for the Media Density variable.
Note
Media Learn may have unexpected results in high temperatures.
Figure 2-4. Fully Immersed Tines for Media Learn
Fast keys
2, 2, 1, 1, 5
OK
Tines Fully
Immersed