Terminal Voltage
.
3.
Follow on-screen instructions to start the simulation.
To start a device variable simulation (LOI)
1.
Press any LOI button to activate the menu.
(See
for assistance with using the LOI buttons).
2.
Scroll down (
) and then select
ENTENDED MENU
(
).
3.
Scroll down (
) and then select
SIMULATE
(
).
4.
Scroll down (
) and select (
) a device variable option:
a.
Output State
.
b.
Sensor State
.
c.
Sensor Frequency
.
d.
Scaled Variable
.
e.
Electronics Temperature
.
f.
Terminal Voltage
.
5.
Follow on-screen instructions to start and end the simulation.
Note
When messages about the loop appear, take appropriate safe action and select “
”.
See
“Configuration basics” on page 10
for further information.
5.5
Diagnostics and service
Diagnostics and service functions listed below are primarily for use after field installation.
For troubleshooting common problems, see also
Section 5: Operation and Maintenance
.
5.5.1
Restart device
The function is used to
reset the electronics
without re-cycling the power.
Note
When messages about the loop appear, take appropriate safe action.
See
“Configuration basics” on page 10
for further information.
To perform a device restart (Field Communicator)
1.
From the Home screen, select
3: Service Tools
.
2.
Select
4: Maintenance
, and then (
6, 7 or 8:) Reset/Restore
.
3.
Select
1: Restart Device
, and follow on-screen instructions to perform the restart.
Summary of Contents for Rosemount 2140
Page 2: ......
Page 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Page 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Page 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Page 143: ......