Application limits
Check for risk of process medium build-up on the level switch forks.
Avoid situations where a drying and coating process medium may create an
excessive build-up (see
) or implement preventative
maintenance programs to ensure the build-up is not enough to impair
performance.
Ensure there is no risk of ‘bridging’ the level switch forks. Examples of products that
can create ‘bridging’ of forks are dense paper slurries and bitumen.
Problems may occur if product coats and dries causing caking.
Ensure the process is operating within the instrument operating temperature and
pressure ranges (see
).
Ensure the liquid viscosity is within the recommended viscosity range
(see
Check that the liquid density is higher than 0.4 SG (400 kg/m
3
)
Liquid density affects the switch-point e.g. dry-to-wet (see
).
The Rosemount 2140 and 2140:SIS are normally insensitive to foams (i.e. they do
not see the foam). However, on rare occasions, some very dense foams may be
seen as liquid; known examples of this are found in ice-cream and orange juice
manufacturing.
Figure 3-2. Level Detection Switching Point
SP: Switching point (H
2
0)
HY: Switching point hysteresis
SP
HY
SP
0.1 in.
(2.5 mm)
0.5 in.
(13 mm)
0.5 in.
(13 mm)
Summary of Contents for Rosemount 2140
Page 2: ......
Page 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Page 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Page 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Page 143: ......