Reference Manual
00809-0100-4140, Rev AA
January 2017
Note
When messages about the loop appear, take appropriate safe action.
See
“Configuration basics” on page 10
for further information.
To start the output state simulation (LOI)
1.
Press any LOI button to activate the menu.
(See
for assistance with using the LOI buttons).
2.
Scroll down (
) and then select
TEST
(
).
3.
Scroll down (
) and then select
LOOP TEST
(
).
4.
Select a loop test option:
a.
Select
SET 4MA
(i.e. 4 mA)
b. Select
SET 20MA
(i.e. 20 mA)
c.
Select
SET CUSTOM
.
5.
Follow on-screen instructions to start and end the simulation.
5.4.5
Simulate device variables
Simulate device variables is only available in HART Revision 7 mode (“HART 7”).
In HART 7, it is possible to temporarily set a device variable to a user-defined fixed value for
testing purposes. After the simulated variable method is exited, the device variable is
automatically returned to a live value.
Simulate Output State
The
Output State
device variable can be temporarily overridden to be “off” or “on”.
Simulate Sensor State
The
Sensor State
device variable can be temporarily overridden to be “dry” or “wet”.
Simulate Sensor Frequency
The
Sensor Frequency
device variable can be temporarily overridden with an entered
frequency in the range 0 to 3000 Hz.
Fast Keys
3, 5
Fast Keys
3, 5, 2
Fast Keys
3, 5, 3
Fast Keys
3, 5, 4
Summary of Contents for Rosemount 2140
Page 2: ......
Page 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Page 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Page 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Page 143: ......