64
Reference Manual
00809-0100-4140, Rev AA
January 2017
4.7.1
Level switch grounding
The most effective grounding method is a direct connection to earth ground with minimal
impedance (< 1
).
shows the two grounding screw connections
provided on the level detector.
Note
Grounding the level detector using a threaded conduit connection may not provide a
sufficient ground.
Figure 4-3. Ground Screws
A. External ground screw
B. Internal ground screw
4.7.2
Signal cable shield grounding
Make sure the instrument cable shield is:
trimmed close and insulated from touching the level detector housing.
continuously connected throughout the segment.
connected to a good earth ground at the power supply end.
Figure 4-4. Cable Shield
A. Trim shield and insulate
C. Trim shield
B. Minimize distance
D. Connect shield back to power supply ground
B
A
A
B
B
C
C
D