Installation recommendations
Avoid installing near to liquid entering the tank at the fill point.
Avoid heavy splashing on the forks.
Increasing the sensor output delay reduces accidental switching caused by
splashing (see
“Sensor output delay” on page 16
).
Ensure that the forks do not come into contact with the tank wall, any internal
fittings, or obstructions.
Ensure there is sufficient distance between build-up on the tank wall and the fork
(see
Ensure the installation does not create tank crevices around the forks where liquid
may collect. This can happen with high-viscosity and high-density liquids.
Extra consideration is needed if the plant vibration is close to the 1400 Hz.
operating frequency of the Rosemount 2140.
Supporting the fork extension tube avoids long fork length vibration
(see