Optional re-mapping of PV
Versions of the Rosemount 2140 with the Extended Features Package (EFP)
can re-map the PV to:
Sensor Frequency
Scaled Variable
Optional re-mapping of SV, TV, or QV
The Rosemount 2140 and Rosemount 2140:SIS can re-map the SV, TV, or QV to:
Output State
Sensor State
Sensor Frequency
Electronics Temperature
Terminal Voltage
Versions of the Rosemount 2140 with the Extended Features Package (EFP)
can also re-map the SV, TV, or QV to:
Scaled Variable
Note
See
“HART (re-mapping dynamic variables)” on page 31
for related information.
2.8
Basic setup
2.8.1
Sensor operation mode
The level detector has three operation modes:
Normal (Rosemount 2140 only)
Default mode with no sensor fault detection enabled.
Enhanced wet
Optional mode where the
Sensor State
device variable is forced to a ‘wet state’
while sensor faults are detected. (Default mode on Rosemount 2140:SIS).
Enhanced dry
Optional mode where the
Sensor State
device variable is forced to a ‘dry state’
while sensor faults are detected.
Note
Sensor State
) is used to derive the
Output State
(
Fast keys
2, 2, 1, 1, 1