71
Reference Manual
00809-0100-4140, Rev AA
January 2017
To start the on-site calibration (Field Communicator)
1.
From the Home screen, select
3: Service Tools
.
2.
Select
4: Maintenance
>
4: Calibrate Analog
.
3.
Select
2: Calibrate
.
4.
Follow on-screen instructions to perform the calibration of 4 mA and 20 mA.
Note
In the Calibrate Analog menu, the
4: Analog Output
option indicates the live output
current output and the
5: Percent Range
option indicates the percentage of that output
current in terms of the complete 4–20 mA range. For example, 8 mA is 25% of range, 12 mA
is 50%, etc.
Note
When messages about the loop appear, take appropriate safe action and select “OK”.
See
“Configuration basics” on page 10
for further information.
To start the on-site calibration (AMS Device Manager)
1.
Right click on the device and select
Service Tools
.
2.
Select
Maintenance
, and then select the
Calibrate Analog
tab.
3.
Click on the
Calibrate
button in the
Analog
box.
4.
Follow on-screen instructions to perform the calibration of 4 mA and 20 mA.
Note
The
Analog Output
device variable indicates the live output current output, and the
Percent of Range
device variable indicates the percentage of that output current in terms
of the complete 4–20 mA range. For example, 8 mA is 25% of range, 12 mA is 50%, etc.
Note
When messages about the loop appear, take appropriate safe action.
See
“Configuration basics” on page 10
for further information.
Summary of Contents for Rosemount 2140
Page 2: ......
Page 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Page 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Page 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Page 143: ......