Differential Pressure
Transmitter to Measure
Flow
Situation
The liquid flow in a line is to be measured using the differential pressure
across an orifice plate in the line, and the flow measurement will be used in a
flow control loop. Based on the orifice specification sheet, the differential
pressure transmitter was calibrated for 0 to 20 in H
2
0 for a flow of 0 to 800
gal/min, and the transducer was not configured to take the square root of the
differential pressure.
Solution
Table D-6 lists the appropriate configuration settings, and Figure D-7
illustrates the correct function block configuration.
Table D-6. Analog Input
Function Block Configuration for
a Differential Pressure
Measurement
Figure D-7. Function Block
Diagram for a Differential
Pressure Transmitter Used in a
Flow Measurement
Parameter
Configured Values
L_TYPE
Indirect Square Root
XD_SCALE
0 to 20 in.
OUT_SCALE
0 to 800 gal/min
38730126
AI
Function
Block
PID
Function
Block
AO
Function
Block
OUT_D
OUT
Analog
Measurement
BKCAL_INBKCAL_OUT
IN
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 12: ......
Page 22: ...Oxymitter 5000 xii Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 42: ...Oxymitter 5000 1 20 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 62: ...Oxymitter 5000 2 20 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 74: ...Oxymitter 5000 4 6 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 78: ...Oxymitter 5000 5 4 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 94: ...Oxymitter 5000 7 6 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 140: ...Oxymitter 5000 9 22 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 184: ...Oxymitter 5000 B 2 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 204: ...Oxymitter 5000 D 14 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 222: ...Oxymitter 5000 E 18 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 224: ...Instruction Manual IM 106 350 Rev 2 2 July 2008 Index 2 Oxymitter 5000 ...