Oxymitter 5000
C-2
Instruction Manual
IM-106-350, Rev 2.2
July 2008
CAL_SLOPE
34.5-57.5
mV/Decade
This parameter represents the slope value
used in the calculation of converting the
sensor voltage to an O2 value. The value of
this parameter may be manually entered or
calculated during a sensor calibration.
26
CAL_STATE
See Table 1
Enumerated
This parameter represents the present state
the calibration cycle is in. Refer to Table 1 for
the definition of states.
19
CAL_STATE_STEP
0: No effect
1: Go to next
step
2: Abort
Calibration
0
Enumerated
This parameter is used to step the
transmitter through a sensor calibration.
Setting this parameter to 1 requests the
transmitter to move to the next cycle state of
the calibration procedure. The request is only
valid when the CAL_STATE value represents
a state that is waiting for an external event
such as the changing of a test gas value. The
transmitter will set this parameter value back
to 0 when it has completed processing the
step request. Setting this parameter to a
value of 2 will cause the present calibration
to be aborted.
20
CAL_STATE_TIME
0-1200
Sec
This is the time in seconds remaining in the
present calibration state.
21
CAL_TRACKS
This parameter is no longer used.
24
CELL_MV_VALUE
± INF
mV
This is the raw signal from the O
2
sensor.
43
CELL_TC_MV_VALUE
-1000.0 - 500.0
mV
This is the raw signal from the O
2
sensor
thermocouple.
44
CELL_TEMPERATURE
This is the current temperature of the O
2
sensor.
54
CHECKSUM
0000
N/A
This is the checksum of the Oxymitter
software.
61
COLD_JUNC_MV_VALUE
± INF
mV
This is the raw signal from the
case/thermocouple cold junction sensor.
45
COLLECTION_DIRECTORY
See Transducer Block Specification, part 1.
FF-902, page 11.
12
CONFIG_CHANGED
0-255
0
N/A
This indicates that a static parameter in the
Oxymitter has changed by some means
other than Fieldbus.
51
TB_DETAILED_STATUS
0-16777215
0
Enumerated
This is a bit-enumerated value used to
communicate the status of the Oxymitter.
(This is similar in nature to the command 48
status bits in HART.)
55
HIGH_CASE_TEMP
0-10000.0
o
C
This is the highest temperature that has been
measured inside the electronics enclosure.
38
Parameter Mnemonic
Valid Range
Initial
Value
Units
Description
Parameter
Number
Summary of Contents for Oxymitter 5000
Page 2: ......
Page 6: ......
Page 12: ......
Page 22: ...Oxymitter 5000 xii Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 42: ...Oxymitter 5000 1 20 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 62: ...Oxymitter 5000 2 20 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 74: ...Oxymitter 5000 4 6 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 78: ...Oxymitter 5000 5 4 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 94: ...Oxymitter 5000 7 6 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 140: ...Oxymitter 5000 9 22 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 184: ...Oxymitter 5000 B 2 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 204: ...Oxymitter 5000 D 14 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 222: ...Oxymitter 5000 E 18 Instruction Manual IM 106 350 Rev 2 2 July 2008 ...
Page 224: ...Instruction Manual IM 106 350 Rev 2 2 July 2008 Index 2 Oxymitter 5000 ...