Configuration and Use Manual
75
Configuring I/O
V
o
lumetr
ic
Flo
w
Measure
ment
Histor
y
, Events, a
n
d Alar
ms
I/
O
Core Interfa
c
e
Table 7-9
Discrete Outputs – General parameters
Parameter
Description
Comments
State
• If Scanning is enabled, State reflects the current output of the
DO, and is updated by the Model 3711.
• If Scanning is disabled, State is not updated by the
Model 3711. Instead, the State setting is used to control the
DO output.
In typical use:
• On = Closed
• Off = Open
Momentary
Off by default. Must be manually set to On. When the On radio
button is enabled and Apply is clicked, the DO switches to On
and remains On for the time period defined in Time On.
Automatically resets to Off after
each activation.
Time On
Used with Momentary and DOUT Type = Toggle:
• Defines the number of seconds that the DO will remain On
when Momentary is activated.
• If DOUT Type is set to Toggle, defines the duration, in
seconds, of the On and Off portions of the DO cycle. In other
words, the DO cycle is twice the Time On value.
When DOUT is not set to Toggle,
this field reflects the current
duration of the DO’s On period.
DOUT Type
• Latched: When the DO switches from Off to On, it remains On
until cleared.
• Time Duration: When a new EU value is written, the DO is
activated once. The length of the On state is defined by the
EU Value parameter.
• Toggle: The DO repeats continuously in a cycle defined by the
Time On parameter. The On and Off states of the cycle are of
equal length.
• TDO Toggle: The DO repeats continuously in a cycle defined
by the Cycle Time parameter, with the length of the On state
defined by the EU Value parameter.
To clear status, click the Off button,
then click Apply.
See Section 7.7.3 for information
on configuring the Time Duration,
Toggle, and TDO Toggle options.
Scanning
• Enabled: The output of this DO will be updated automatically,
according to the current EU value.
• Disabled: The output of this DO is not updated from the
current EU value. The output of the DO is controlled by the
configured State value.
If Alarming is enabled, an alarm is
generated when Scanning is set to
Disabled.
Active Alarms
Displays any alarms that are currently active for this point.
The field at the right of the Active
Alarm field displays the alarm bit
status value (0 to 255).
Summary of Contents for Micro Motion 3711
Page 32: ...24 Micro Motion Model 3711 Gas Flow Computers ...
Page 44: ...36 Micro Motion Model 3711 Gas Flow Computers ...
Page 56: ...48 Micro Motion Model 3711 Gas Flow Computers ...
Page 68: ...60 Micro Motion Model 3711 Gas Flow Computers ...
Page 92: ...84 Micro Motion Model 3711 Gas Flow Computers ...
Page 108: ...100 Micro Motion Model 3711 Gas Flow Computers ...
Page 140: ...132 Micro Motion Model 3711 Gas Flow Computers ...
Page 196: ...188 Micro Motion Model 3711 Gas Flow Computers ...
Page 210: ...202 Micro Motion Model 3711 Gas Flow Computers ...
Page 233: ......