Configuration and Use Manual
63
Configuring I/O
V
o
lumetr
ic
Flo
w
Measure
ment
Histor
y
, Events, a
n
d Alar
ms
I/
O
Core Interfa
c
e
Figure 7-2
Analog Input – General panel
1. Use the
Analog Inputs
dropdown list to select the AI to configure.
•
To configure the built-in pressure sensors, select
Line Press
or
Aux Press
.
•
To configure an external RTD input using the built-in RTD terminals, select
RTD
.
•
To configure the analog inputs on the I/O board, select
Aux In 1
or
Aux In 2
.
2. Enter the tag to be used to describe this input.
3. Work through the configuration panels in the following order:
•
General
•
Advanced
•
Alarms
Note: To calibrate the AI, see Appendix B.
7.4.1
Filtering
The Model 3711 automatically filters analog input data using the following formula:
where
Entered %
is the value specified for
Filter
on the Advanced panel. The resulting value (the
Filtered Value
) is used for display and further processing.
This calculation is updated once per Scan Period, as configured on the General panel (see
Section 7.4.2).
Many remote devices also have a filtering algorithm. If a filter is applied at both the remote device
and the Model 3711, measurement accuracy may be reduced. To disable the filter in the Model 3711,
enter 0 in the Filter field (see Section 7.4.3).
LastValue
Entered%
×
(
)
NewValue
100
Entered%
–
(
)
×
[
]
+
Summary of Contents for Micro Motion 3711
Page 32: ...24 Micro Motion Model 3711 Gas Flow Computers ...
Page 44: ...36 Micro Motion Model 3711 Gas Flow Computers ...
Page 56: ...48 Micro Motion Model 3711 Gas Flow Computers ...
Page 68: ...60 Micro Motion Model 3711 Gas Flow Computers ...
Page 92: ...84 Micro Motion Model 3711 Gas Flow Computers ...
Page 108: ...100 Micro Motion Model 3711 Gas Flow Computers ...
Page 140: ...132 Micro Motion Model 3711 Gas Flow Computers ...
Page 196: ...188 Micro Motion Model 3711 Gas Flow Computers ...
Page 210: ...202 Micro Motion Model 3711 Gas Flow Computers ...
Page 233: ......