Configuration and Use Manual
69
Configuring I/O
V
o
lumetr
ic
Flo
w
Measure
ment
Histor
y
, Events, a
n
d Alar
ms
I/
O
Core Interfa
c
e
Figure 7-6
Analog Outputs – Advanced panel
Table 7-5
Analog Outputs – Advanced parameters
Parameter
Description
Comments
Raw D/A Output
The current value produced by the Digital-to-Analog converter.
Read-only.
Adjusted D/A 0%
The Digital-to-Analog value corresponding to 0% output.
Used in conversion of EUs to an
analog signal.
Adjust this value as required for
agreement between the
Model 3711 and the remote
device. See Section B.3.
Adjusted D/A
100%
The calibrated Digital-to-Analog reading corresponding to 100%
output.
Used in conversion of EUs to an
analog signal.
Adjust this value as required for
agreement between the
Model 3711 and the remote
device. See Section B.3.
Value on Power
Reset
Specifies the startup value to be used by this AO if a power
reset or warm start occurs.
• Low EU: The Low EU value is
used to calculate the startup AO
signal.
• Retain Last Value: The last EU
value before the power reset is
used to calculate the startup AO
signal.
RBX Alarming
Specifies the type of Report By Exception alarming for this
output:
• Disabled – No RBX alarming.
• On Alarm Set – RBX alarm generated when the analog output
enters an alarm condition.
• On Alarm Clear – RBX alarm generated when the analog
output leaves an alarm condition.
• On Alarm Set and Clear – RBX alarm generated when the
analog output enters an alarm condition and when the analog
output leaves an alarm condition.
If RBX Alarming is enabled, a
communications port must be
configured for RBX alarming. See
Section 4.6
Summary of Contents for Micro Motion 3711
Page 32: ...24 Micro Motion Model 3711 Gas Flow Computers ...
Page 44: ...36 Micro Motion Model 3711 Gas Flow Computers ...
Page 56: ...48 Micro Motion Model 3711 Gas Flow Computers ...
Page 68: ...60 Micro Motion Model 3711 Gas Flow Computers ...
Page 92: ...84 Micro Motion Model 3711 Gas Flow Computers ...
Page 108: ...100 Micro Motion Model 3711 Gas Flow Computers ...
Page 140: ...132 Micro Motion Model 3711 Gas Flow Computers ...
Page 196: ...188 Micro Motion Model 3711 Gas Flow Computers ...
Page 210: ...202 Micro Motion Model 3711 Gas Flow Computers ...
Page 233: ......