42
Micro Motion
®
Model 3711 Gas Flow Computers
Configuring the Core Interface
Figure 5-4
Temperature panel
Table 5-3
Temperature configuration parameters
Parameter
Description
Comments
Damping Period
The number of seconds over which the reported temperature
value will change to reflect 63% of the change in the actual
process. See Section 5.5.2.
Default: 4.8 seconds
Calibration Slope
The slope value used to adjust the temperature process
variable.
Default: 1.0
Calibration Offset
The offset value used to adjust the temperature process
variable.
Default: 0.0
External
Temperature
• Disabled: Temperature data from the Micro Motion sensor will
be used.
• Enabled: Temperature data from a different temperature
device will be used. If Enabled is specified, a Source field is
displayed. Use the Select TLP dialog box to specify the
temperature source. The Value field displays the current
temperature value from the specified source.
Applies to all Model 3711
calculations that require a
temperature value.
Summary of Contents for Micro Motion 3711
Page 32: ...24 Micro Motion Model 3711 Gas Flow Computers ...
Page 44: ...36 Micro Motion Model 3711 Gas Flow Computers ...
Page 56: ...48 Micro Motion Model 3711 Gas Flow Computers ...
Page 68: ...60 Micro Motion Model 3711 Gas Flow Computers ...
Page 92: ...84 Micro Motion Model 3711 Gas Flow Computers ...
Page 108: ...100 Micro Motion Model 3711 Gas Flow Computers ...
Page 140: ...132 Micro Motion Model 3711 Gas Flow Computers ...
Page 196: ...188 Micro Motion Model 3711 Gas Flow Computers ...
Page 210: ...202 Micro Motion Model 3711 Gas Flow Computers ...
Page 233: ......