Edit the Liebert IntelliSlot Unity Card Configuration
Liebert
®
IntelliSlot
®
Unity
™
Card
34
5.5
Unity Tab—Protocols
The Protocols folder displays the types of protocols that may be enabled for a Liebert IntelliSlot Unity
card. Not all protocols are available at the same time. Some protocols may not be available for some
types of managed devices (see
1.2 - Compatibility With Other Emerson Products and
Communication Protocols
). The Liebert IntelliSlot Unity card allows selecting two third-party
protocols.
The folders contained by the Protocols folder are:
• BACnet
• BACnet IP
• BACnet MSTP
• Modbus
• Modbus TCP
• Modbus RTU
• SNMP
• SNMPv3 User Settings (20)
• SNMPv1 Trap Settings (20)
• SNMPv1/v2c Access Settings (20)
• YDN23
Settings in each permit configuring the protocols available on the Liebert IntelliSlot Unity card.
5.6
Protocols Folder—BACnet Folder
BACnet Settings
• Managed Device Write Access—Enable or Disable the BACnet server to write to the managed
device.
• BACnet Interface—BACnet server interface: BACnet IP or BACnet MSTP.
• Device Object Instance Number—The instance number (0-4194302) of the BACnet server's device
object.
• Device Object Name—The name of the BACnet server's device object.
• APDU Timeout—The timeout in milliseconds between APDU retries (1-65535).
• APDU Retries—The number of times to retransmit an APDU after the initial attempt (0-8).