Enable Communication Protocols
Liebert
®
IntelliSlot
®
Unity
™
Card
12
Figure 6
Modbus TCP-Trusted IP List
Configure Modbus RTU
1. Select the Unity Tab > Protocols > Modbus RTU.
2. Click on
Edit
and enter a user name and password if required.
3. Set the Node ID and the Baud Rate.
The Node ID defaults to 1, but must have a value from 1 to 255 that is unique among devices
connected through the RS-485 interface.
The default baud rate is 9600; 19200 and 38400 also available.
Contact your system administrator if you are uncertain about the settings.
4. Click
Save
to confirm the changes or click on
Cancel
to discard them.
5. Restart the card to confirm the changes.
a. Select Unity Tab > Support.
b. Enable the commands.
c. Click on
Restart
.
... brings up a screen
where this information
may be entered.
Clicking on
one of the
five Trusted
IP List
folders ...