Enable Communication Protocols
13
Liebert
®
IntelliSlot
®
Unity
™
Card
Figure 7
Modbus-RS-485
3.1.2 Enable BACnet Protocol
Contact your system administrator or building management system administrator if you are
uncertain about the settings.
1. Select Unity Tab > Protocols > BACnet.
2. Click on
Edit
and enter a user name and password if required.
3. Enter the Managed Device Write Access level (Read Only or Read/Write). This determines a
user’s ability to change settings in the Liebert IntelliSlot Unity card.
4. Choose the BACnet interface, either BACnet IP or BACnet MSTP
5. Set the Device Object Instance Number.
6. Set the Device Object Name.
7. Set the APDU Timeout.
8. Set the APDU Retries.
9. Click
Save
to confirm the changes or click on
Cancel
to discard them.
10. Configure the BACnet interface chosen; refer to
Configure BACnet IP Protocol
or
Configure
BACnet MSTP Protocol
. For additional details, see
5.6 - Protocols Folder—BACnet Folder
.
Node ID must
be unique on
the RS-485 bus
this card is
connected to.